Abstract
The developments in HVDC transmission are expected to extend to MV level in the future, where MVAC cables can be used for MVDC. In this regard, the DC conductivity is an important parameter for evaluating DC cable insulation and it is determined through DC leakage current measurements. This study evaluates the impact of accessories on the DC leakage current of MVDC XLPE cable systems. Therefore, one cable system with and one without a joint was set up to examine the influence of a joint and terminations on the leakage current. The investigation is significant due to the potential presence of accessories in future MVDC cable systems. Furthermore, this study presents leakage current measurement as a diagnostic tool that may allow for quick and efficient detection of cable degradation during operation.
| Original language | English |
|---|---|
| Title of host publication | 2024 10th International Conference on Condition Monitoring and Diagnosis, CMD 2024 |
| Publisher | IEEE Xplore |
| Pages | 215-218 |
| Number of pages | 4 |
| ISBN (Electronic) | 978-8-9865-1022-5 |
| DOIs | |
| Publication status | Published - Dec 2024 |
| Event | 10th International Conference on Condition Monitoring and Diagnosis, CMD 2024 - Gangneung, Korea, Republic of Duration: 20 Oct 2024 → 24 Oct 2024 Conference number: 2024 https://www.cmd2024.org/ |
Conference
| Conference | 10th International Conference on Condition Monitoring and Diagnosis, CMD 2024 |
|---|---|
| Abbreviated title | CMD 2024 |
| Country/Territory | Korea, Republic of |
| City | Gangneung |
| Period | 20/10/24 → 24/10/24 |
| Internet address |
ASJC Scopus subject areas
- Electrical and Electronic Engineering
- Electronic, Optical and Magnetic Materials
- Safety, Risk, Reliability and Quality
Keywords
- DC conductivity
- DC leakage current measurements
- diagnostic tool
- MVDC cable systems
- XLPE insulated cable
Cite this